IAS 2 Dual channel detector to accommodate two standard Addressable or Conventional smoke detectors.
The ICAM IAS by Xtralis aspirating smoke detector (ASD)provides a flexible solution to meet the unique needs of numerous applications including commercial spaces such as elevator shafts, the tamper-proof and unobtrusive requirements of special accommodations, or can simply be used to replace spot (point) detectors in office environments. The IAS uses client's existing FIP (fire indicator panel), infrastructure (smoke points), and provides the advantages associated with ASD principles/applications.
Model Numbers: IAS-1, IAS-2
Specifications
Supported detectors:
• 1 or 2 analog addressable or conventional spot (point) detectors
• a variety of detector technology types (photoelectric, ionization, heat, CO etc.)
• spot (point) detectors with universal screw mounting
Supply Voltage:
24 VDC nominal (18 to 30 VDC)
Note that spot (point) detectors are powered from the signaling circuit
Current:
300 mA (max)
Dimensions (WHD):
259 mm x 184 mm x 166 mm (10.2 in. x 7.2 in. x 6.5 in.)
Operating Conditions:
Temperature: -10 to 60 °C (14 to 140 °F) Humidity: 10 to 95% RH (noncondensing)
Inlet Pipe Size:
Outer Diameter: 25 mm (0.98 in.) Inner Diameter: 21 mm (0.83 in.)
Sampling Network:
Pipe Length: Up to 100 m (328 ft) per inlet
Pipe length may vary subject to specifications by local codes and standards, please refer to your regional IAS product guide for further detail.
IP Rating:
IP65
Filtration:
Serviceable filter
External filter optional
Flow Monitoring and Reporting:
High and Low adjustable
Fan:
Control: 10 programmable speeds
Pressure: 250 Pa
Relay outputs:
IAS-1 - 1 fault relay
IAS-2 - 2 fault relays
SUPPLY 18-30V DC
300mA MAX @ MAX FAN SPEED