Currently Viewing Product 7 of 9
AD-99-2270: TT-015L TopSens Silent (High Sensitivity)
Model: AD-99-2270
QTY :
TT-015L TopSens Silent (High Sensitivity c/w 0.015% Detector)
Applications
The complete TITANUS TOP·SENS® offers a comprehensive product range along with accessories approved in accordance with EN 54-20. This allows the device to be used in areas where other smoke detectors and air sampling smoke detection systems have long reached their limits. These include:
- IT areas and clean rooms
- General warehouses, high bay storage areas and
- cold storage areas
- Production and assembly lines
- Wind farms
- Libraries, museums and archives
- Hospitals, hotel rooms and saunas
- Recycling areas
- Rail vehicles and tunnels
Basic equipment | TITANUS TOP-SENS® | TITANUS TOP·SENS® 2 |
---|---|---|
Number of Detector Modules | 1 | 2 |
max. number of sampling holes | 32 | 64 |
max. pipe length (with max. number of sampling holes) | 300 m | 560 m |
Monitored area per sampling hole | Corresponds to one point-type smoke detector in accordance with VDE 0833-2 | |
Monitoring of pipe systems for breakage and obstruction | Optional adjustment for individual hole monitoring** | |
Double-knock detection | Possible using detector box | Yes (separate room and equipment protection) |
Sensitivity detection unit DM-TT-01 - (Sampling holes in accordance with EN 54-20: - Classes A max. 2 x 32, B max. 2 x 32 and C max. 2 x 32) | Info-alarm: 0.005 % LT/m* | |
Pre-alarm: 0.01 % LT/m* | ||
Main alarm: 0.015 % LT/m | ||
Sensitivity detection unit DM-TT-10 - (Sampling holes in accordance with EN 54-20: - Class A max. 2 x 9, Class B max. 2 x 32, Class C max. 2x32) | Info-alarm: 0.03 % LT/m* | |
Pre-alarm: 0.07 % LT/m* | ||
Main alarm: 0.01 % LT/m | ||
Sensitivity detection unit DM-TT-50 - (Sampling holes in accordance with EN 54-20: - Class A max. 2 x 4, Class B max. 2 x 12, Class C max. 2x32) | Info-alarm: 0.17 % LT/m* | |
Pre-alarm: 0.3 % LT/m* | ||
Main alarm: 0.5 % LT/m | ||
Alarms (Volt free C/O) | Up to 3 alarms per detector module (Info, Pre and main alarm)* | |
Fault alarms | Common Alarm (1 x volt free contact per module, NC or NO) | |
Alarm and fault relay power rating | 1 A, 30 V DC, max. 24 W | |
Clamped connections | Max. 1.5 mm² | |
Displays on device | ||
- Info, pre-alarm and main alarm | 1 red alarm display per detector module | |
- Smoke level | 10-step bar graph display | |
- Fault | Yellow collective fault | |
- Operation | Green operation display | |
Operating voltage | 24 V DC (14 - 30 V DC) | |
Max. quiescent current (at 24 V DC) | 200 mA | 230 mA |
Max. alarm current (at 24 V DC) | 230 mA | 290 mA |
Starting current limted to | 300 mA | 330 mA |
Dimensions (W x H x D) | 200 x 292 x 113 | |
Weight | 1460 g | 1560 g |
SL Version | ||
Max. quiescent current (at 24 V DC) | 160 mA | 200 mA |
Max. alarm current (at 24 V DC) | 190 mA | 230 mA |
Starting current limted to | 300 mA | 300 mA |
Noise Levels (with sound damper) | from 23 dB (A) | |
Protection category | IP20 (optional IP52) | |
Temperature range | -20 °C to + 60 °C | |
Cold storage option (No SL ver) | -40 °C to + 60 °C | |
Humidity (permanent) | 10 % to 95 % relative humidity | |
Event log | Built-in, additional external data storage possible | |
Connection of external alarm notifications | Parallel display optional | |
Network capability | Able to accept an ethernet network card | |
Approved in accordance with EN 54-20, Classes A, B, C: | ||
- VdS-No. | G 206004 | |
- BPRI-No. | 0786-CPD-20685 | |
* At standard fan voltage 6.9 V fan ** depending on project design |
Shipping Weight: 2000gms