Applications
The compact TITANUS MICRO·SENS® is ideal for applications where larger air sampling smoke detection systems would not be cost-effective or in situations that require individual room identification.
- Small to medium-sized spaces up to 400 m² (e.g. IT areas, server rooms)
- Equipment (e.g. switch cabinets, telecommunications equipment)
- Up to 5 adjacent rooms with localisation of the source of the fire (e.g. hotel rooms, offices, prison cells)
- Stand-alone areas of application (e.g. wind farms, transformer stations)
Basic equipment | TITANUS MICRO·SENS® |
---|---|
max. number of sampling holes | 8 |
max. pipe length (with max. number of sampling holes) | 50 m |
Localisation using ROOM·IDENT | Monitoring of up to 5 rooms with localisation of the source of the fire* |
Monitored area per sampling hole | Corresponds to one point-type smoke detector in accordance with VDE 0833-2 |
Monitoring of pipe systems for breakage and obstruction | Optional adjustment for individual hole monitoring** |
Double-knock detection | Possible using detector box |
Sensitivity detection unit DM-TM-10 | |
- (Sampling holes in accordance with EN 54-20: | Pre-alarm*: 0.05 % LT/m |
- Classes A max. 2, B max. 6 and C max. 8) | Main alarm: 0.10 % LT/m |
Sensitivity detection unit DM-TM-50 | |
- (Sampling holes in accordance with EN 54-20: | Pre-alarm*: 0.25 % LT/m |
- Class A max. 2, Class B max. 6, Category C max. 8) | Main alarm: 0.50 % LT/m |
Alarm notification | 1-2 (Pre and main alarm)* |
Potential free contacts, internal (external, optional) | 2 (5) |
Fault alarms | Cumulative report (Potential free contact, either via NC or NO) |
Alarm and fault relay power rating | 1 A, 30 V DC, max. 24 W |
Clamped connections | Max. 2.5 mm² |
Displays on device | |
- Pre-alarm and main alarm | 1 red alarm display for each* |
- Smoke Level | 10-step bar graph display* |
- Fault | Yellow common fault |
- Operation | Green operation display |
Operating voltage | 24 V DC (16 - 30 V DC) |
Max. quiescent current (at 24 V DC) | 105 mA (at standard fan voltage of 9 V) |
Max. alarm current (at 24 V DC) | 110-140 mA (at standard fan voltage of 9 V)* |
Starting current | 150 mA |
Dimensions (W x H x D) | 140 x 222 x 70 mm³ |
Weight | 850 to 895 g* |
Protection category | up to IP 54 |
Temperature range | -20 °C to + 60 °C |
Cold storage option | -40 °C to + 60 °C |
Humidity (permanent) | 10 % to 95 % relative humidity |
Event log | Built-in |
Connection of external alarm notifications | Parallel displays and ROOM·IDENT indicators optional |
Network capability | Able to accept an Ethernet network card |
Redundant fan | Built-in* |
Approved in accordance with EN 54-20, Classes A, B, C: | |
- VdS-No. | G 206004 |
- BPRI-No. | 0786-CPD-20322 |
* depending on device configuration ** depending on project design |
Shipping Weight: 1000gms